S11 Oil-Immersed Distribution Transformer

The company manufactures production of S11 - M series the whole sealing oil-immersed power transformer has the advantages of low loss, low noise, high efficiency, can obtain good energy saving effect and reduce pollution.
Availability:
Product Description

Product overview
The company manufactures production of S11 - M series the whole sealing oil-immersed power transformer has the advantages of low loss, low noise, high efficiency, can obtain good energy saving effect and reduce pollution. Totally enclosed comparing with ordinary oil-immersed transformer, cancel the oil storage tank, the oil volume changed by corrugated tank elastic corrugated chips to automatically adjusting, transformer is isolated from the rest of the air, to prevent and slow the deterioration of oil and insulation aging, enhance the operation reliability.

Standards
GB 1094 power transformer
GB/T 15164 oil-immersed power transformer load guide book
GB/T 6451 three-phase oil-immersed power transformer technical parameters and requirements
GB 2536 transformer oil
GB 311.1 high voltage power transmission and transformation equipment insulation coordination
JB/T 501 power transformer experimental guide books
GB 10237 power transformer insulation level and external insulation insulation experiments of air gap
DL/T 572 transformer operation procedures

Product features
1. Transformer core uses the import high quality cold rolled silicon steel sheet pile, and greatly reduce no-load loss and no-load current, and the core are binding, guarantee the iron core of compactness, and reduce noise.
2. High and low voltage winding with oxygen frees copper winding, low voltage winding double cylinder structure is used to 500 kva and below. More than 630 kva and adopts double helix or four helical structure, high voltage winding adopts multilayer cylindrical structure.
3. Transformer connection group uses the Dyn11, reduce the influence of the harmonic of power grid, and improve the quality of power supply.
4. Transformer is fully sealed structure, prolong service life, avoid hanging core, maintenance free.
5. The measured noise value is lower than the standard.
This series transformer after normal transportation, do not need to lift core check, can install the relevant parts and components, project acceptance test, after qualified can be put into operation.

Conditions of use

1. The highest temperature: + 40 ℃
2. The lowest temperature: 25 ℃
3. Altitude: < 1000 m
4. The highest monthly average relative humidity: 90% (20 ℃)
5. Installation location: installed in no fire and explosion danger, serious foul, chemical corrosion and the site of violent vibration, indoor or outdoor.

S11 type 6-11kV kv double winding series main performance parameters of the products

Type

Rated capacity
          (KVA)

Connection symbol

Voltage combination
          (KV)

No-load losses(W)

Load losses(W)

No- load current (%)

Short-circuit impedance
          (%)

H.V

Tapping range

L.V

S11-M-30

30

Yyn0 or
           Dyn11

6

6.3

10

10.5

11

±5% or

±2×2.5%


0.4

100

600

2.3

4.0

S11-M-50

50

130

870

2.0

S11-M-63

63

150

1040

1.9

S11-M-80

80

180

1250

1.9

S11-M-100

100

200

1500

1.8

S11-M-125

125

240

1800

1.7

S11-M-160

160

280

2200

1.6

S11-M-200

200

340

2600

1.5

S11-M-250

250

400

3050

1.4

S11-M-315

315

480

3650

1.4

S11-M-400

400

570

4300

1.3

S11-M-500

500

680

5100

1.2

S11-M-630

630

810

6200

1.1

4.5

S11-M-800

800

980

7500

1.0

S11-M-1000

1000

1150

10300

1.0

S11-M-1250

1250

1360

12800

0.9

S11-M-1600

1600

1640

14500

0.8

S11-M-2000

2000

2280

17820

0.6

5.0

S11-M-2500

2500

2700

20700

0.6


S11 type 15-22 kv double winding series main performance parameters of the products

Type

Rated capacity
          (KVA)

Connection symbol

Voltage combination(KV)

No-load losses(W)

Load losses(W)

No- load current(%)

Short-circuit impedance
          (%)

H.V

Tapping range

L.V

S11-M-30

30

Dyn11

15
          20
          22

±5% or

±2×2.5%


0.4

90

660

2.1

5.5

S11-M-50

50

130

960

2.0

S11-M-63

63

150

1145

1.9

S11-M-80

80

180

1370

1.8

S11-M-100

100

200

1650

1.6

S11-M-125

125

240

1980

1.5

S11-M-160

160

290

2420

1.4

S11-M-200

200

330

2860

1.3

S11-M-250

250

400

3350

1.2

S11-M-315

315

480

4010

1.1

S11-M-400

400

570

4730

1.0

S11-M-500

500

680

5660

1.0

S11-M-630

630

810

6820

0.9

6.0

S11-M-800

800

980

8250

1.8

S11-M-1000

1000

1150

11330

0.7

S11-M-1250

1250

1350

13200

0.7

S11-M-1600

1600

1630

15950

0.6


Previous: 
Next: 

Product Category

Send Us A Message

About Company

ALL THE EFFORTS OF HUACHEN PEOPLE,
ALL FOR CUSTOMER SATISFACTION.
 

Quick Links

Product Category

Contact Us

 Tongshan Economic Development Zone Industrial Park , No. 2 Qianjiang Road, Xuzhou, Jiangsu Province,China
  marketing_huachenjs@hcbyq.com
  +86-15852157931
  +86-516-69687778
 Wechat/ Skype/Zalo: +86 15852157931
Whatsapp:+86 15852157931
      
Copyright © 2022 Jiangsu Huachen Transformer Co.,Ltd. All rights reserved. 苏ICP备07503629号-8   Support by leadong | Sitemap
We use cookies to enable all functionalities for best performance during your visit and to improve our services by giving us some insight into how the website is being used. Continued use of our website without having changed your browser settings confirms your acceptance of these cookies. For details please see our privacy policy.
×